Home < Temperature & Humidity < Transmitter and Light Industrial
Features : Multifunction physical quantities ─ temperature & humidity /dew point / frost point /wet-bulb temp. / vapor pressure /mixture ratio /absolute humidity / specific enthalpy.
Input :Capacitive Humidity Sensor & PT 100Ω class A
Output :standard RS-485 or 2 analog output
( 0 ... 20 mA / 4 ... 20mA / 0 ... 1V / 0 ... 5V / 0 ... 10V )
Linear Accuracy (at 25°C) :
temperature ± 0.2 °C ± 0.005 °C x t actua /
humidity ( at + 25 °C ) ± 2 %RH
Working Range Suggestion :
temperature 0 ... 50 °C ( THS301 );
- 40 ... + 80 °C ( THS302 ) ;- 40...+ 80 °C ( THS304 / 307 ) /
humidity : 0 ... 100 %RH / dew point - 40 ... + 60 °C /
Frost Point ( F )、Wet-bulb Temperature ( W )、Vapor Pressure ( E )、Mixture Ratio ( R )、
Absolute Humidity ( V )、Specific Enthalpy ( S ) :
please refer to physical quantity measuring range list
High-performance Integrated Indicator Transmitter Series with Anti-interference Design
Input : Temp. 、Pressure、Differential Pressure、 Level
Output : 4 ... 20 mA
Display Range : -9999 ... 99999
Accuracy :
Feature : Stable & Accurate Performance in Explosion Hazardous Areas
Input : Capacitive Humidity Sensor & PT 1000Ω
Output : 4 ... 20 mA
Range :
Temperature:-20 ... +80°C
Humidity: 0 ... 100 %RH
Accuracy :
Temperature:±0.3°C+0.002°C x t actual
Humidity:±2% RH(15 ... 90 %)
Feature : Industrial-grade Metal Meter/Can be connected to a 2-wire transmitter/Anti-interference Design/Multiple Input Type
Input : 4 ... 20 mA DC Temperature / Pressure / Differential pressure / Flow, etc.
Range : -1999 ... +9999
Accuracy : 0.2 % F.S
Features : IP65 protection degree / Process temp. : up to 200℃ / S.S. probe proof pressure : 10 bar, metal connector
Input : Capacitive Humidity Sensor & PT 100Ω A class
Output : 0 ... 20 mA / 4 ... 20 mA / 0 ... 1 V / 0 ... 5 V / 0 ... 10 V
Accuracy ( at +25 °C ) :
temperature ± 0.15 °C ± 0.002 °C x t actul /
humidity ( 0 ... 90 % ) nonlinear error : ± 1.2 % RH ;
hysteresis error : ± 0.8 % RH ; repeatability error : ± 0.4 % RH /
humidity ( 90 ... 100 %) ± 2 % RH /
thermal sensitivity temperature error 0.05 % RH / °C
Factory Uncertainty ( at +25 °C ) :
temperature uncertainty 0.14 °C /
humidity uncertainty 0.4 % RH ( >10 % ... 20 % ) ;
0.65 % RH ( >20 % ~ 90 % ) ; 0.97 % RH ( >90 % ~ 98 % )
Features : Double anti-condensation, CMOS wafer
Range : 0 ... + 50℃ ; 0 ... 100 %RH ( non-cond. )
Accuracy : ± 0.5℃ ; ± 5 %RH
Housing : PC, Fire-proof, HB Class ; Probe : SUS304
Filter : PC+Glass fiber, Temp. up to 120 ℃
Material of Probe kit PE with dew environmental protection